4/0-4/0-2/0 Aluminum SER Cable (Service Entrance Style R) is a 600V multi-conductor cable consisting of two insulated 4/0 AWG 18-strand conductors (black and red) and one bare 2/0 AWG 18-strand equipment grounding conductor. Because it does not contain a dedicated white neutral conductor, it is specifically used for 240V single-phase branch circuits and subpanels that do not serve 120V line-to-neutral loads—such as 180A–200A electric furnaces, large heat pumps, commercial HVAC units, and 240V equipment panels. (Note: If your subpanel feeds 120V circuits, you will need 4/0-4/0-4/0-2/0 SER, which includes three insulated conductors plus a ground.)
Per NEC Table 310.16 and Article 338.10, 4/0 AWG aluminum SER Cable conductors are rated for 180 Amps at 75°C and 205 Amps at 90°C for general feeder applications (and 200 Amps when qualifying as a 120/240V main residential dwelling feeder under NEC Table 310.12). Because standard circuit breakers and panelboard lugs are rated for 75°C terminations under NEC 110.14(C), 4/0-4/0-2/0 Aluminum SER is typically protected by a 180-amp or 200-amp breaker (per NEC 240.4(B) next-size-up rules where applicable) in standard installations.
Important NEC Note: Per NEC 338.10(B)(4)(a) and NEC 334.80, interior SER cable installed in thermal insulation is governed by the 60°C ampacity column of NEC Table 310.16 (150 Amps for 4/0 AWG aluminum). Always consult a licensed electrician or local Authority Having Jurisdiction (AHJ) to verify exact breaker sizing, voltage drop, and local code compliance before installation.
SER (Service Entrance Style R) is a round cable assembly containing insulated conductors cabled around a bare equipment grounding conductor, designed primarily for interior panel feeders and branch circuits. SEU (Service Entrance Style U) is a flat cable featuring two insulated conductors wrapped in a concentric neutral/ground ribbon, typically used for main overhead service drops where the neutral and ground are bonded at the main disconnect. For a full breakdown of code applications and sizing rules, read our SER vs. SEU cable guide.
No. Type SER Cable is listed under UL 854 for above-ground installation only. While its XHHW-2 internal conductors and gray PVC outer jacket are rated for wet and sunlight-resistant exterior locations, SER is not rated for direct burial or underground conduit installations. For underground runs, use Aluminum URD or USE-2 / RHH / RHW-2 conductors.
While modern AA-8000 series aluminum alloy does not strictly require oxide-inhibiting compound under NEC rules unless specified by the connector manufacturer, applying an approved antioxidant paste (such as Penetrox) and torquing all AL7CU / AL9CU dual-rated lugs to exact manufacturer specifications is best industry practice to ensure long-term connection integrity.
Wire America stocks master reels of AA-8000 Aluminum SER Cable ready for rapid commercial, multi-family, and residential jobsite fulfillment: