"The industry standard for 120/240V single-phase overhead utility drops, residential main power feeds, and temporary jobsite distribution. Engineered for dependable 600V aerial power delivery from utility lines to building weatherheads, this 3-conductor triplex cable features two solid aluminum phase conductors, weather-resistant XLP insulation, and a heavy-duty bare steel-reinforced ACSR neutral messenger built to withstand environmental strain."
Key Features & Benefits: 6-6-6 Solid Triplex Overhead Service Drop Cable
The 6-6-6 Paludina Solid Triplex Cable is designed for overhead single-phase 120/240V secondary power distribution where solid phase conductors are preferred. Built to span overhead gaps from utility pole transformers to residential weatherheads and service masts, it provides a stable, sag-resistant solution for main service drops and temporary construction power feeds.
By pairing two solid 1350-H19 series aluminum phase conductors with a high-tensile ACSR neutral messenger, Paludina triplex provides lightweight, low-maintenance power delivery with maximum physical durability. The cross-linked polyethylene (XLP) insulation offers superior protection against sunlight, freezing rain, and severe atmospheric wear.
600V Aerial Reliability: Rated for continuous 120/240V aerial service (up to 600V max phase-to-phase) at conductor temperatures up to 90°C with XLP insulation.
High-Tensile ACSR Messenger: Features a 6/1 steel-reinforced ACSR neutral messenger delivering 1,190 lbs of breaking strength to prevent sag and withstand heavy ice and wind loads.
Sunlight & Weather-Resistant XLP: Heavy-duty black cross-linked polyethylene insulation prevents UV degradation, cracking, and moisture damage in outdoor environments.
Cut to Length by the Foot: Order only the exact span length needed for your project, eliminating jobsite waste and unused spools.
Technical Specifications: Paludina 6-6-6 Solid Triplex Overhead Cable
Application: Overhead secondary power drops (120/240V single-phase) from utility pole to weatherhead, temporary jobsite power, and outbuilding service feeds.
Code Word: Paludina.
Voltage Rating: 600 Volts Maximum (Phase-to-Phase).
Phase Conductors Size & Stranding: Two (2) #6 AWG Solid (1350-H19 Series Aluminum).
Neutral Messenger Size & Stranding: One (1) #6 AWG ACSR (6 Aluminum / 1 Steel Strand).
Messenger Breaking Strength: 1,190 lbs.
Insulation Material: Black Cross-Linked Polyethylene (XLP).
Insulation Thickness: 0.045 inches (1.14 mm).
Nominal Outer Diameter: 0.53 inches.
Approximate Cable Weight: 114 lbs per 1,000 ft.
Ampacity (90°C XLP Conductor): 85 Amps.
Ampacity (75°C Poly Conductor): 70 Amps.
Compliance & Standards: ASTM B-230, ASTM B-231, ASTM B-232, ICEA S-76-474, RUS Accepted.
Common 6-6-6 Solid Triplex Overhead Applications
Residential Overhead Service Drops: 120/240V single-phase power runs from utility pole transformers to residential weatherheads or outbuilding subpanels.
Temporary Construction Power: Heavy-duty overhead power delivery for temporary service poles and main jobsite power distribution panels.
Agricultural & Detached Buildings: Aerial power supply to workshops, barns, and detached garages.
Â
Technical Note: All values are nominal and subject to industry tolerances and manufacturer corrections. Specifications are subject to change without notice. It is the buyer’s responsibility to verify that all materials meet the specific requirements of the project and comply with local electrical codes.
Ampacity Reference: Based on conductor temperature of 90°C for XLP (75°C for Poly), 40°C ambient temperature, 0.9 emissivity, and 2 ft/sec wind in full sun. Reference applicable NEC articles for site-specific installation guidelines.