4/3 NM-B Copper Building Wire with Ground, 600V (Black Jacket)

Parent SKU :  NMB4-3

SKU :  NMB4-3-250

STRANDED COPPER • 600V • NON-METALLIC SHEATHED CABLE
Wire Size 4 AWG
Conductor Material Copper
Conductor Type Stranded
Outer Diameter 0.72 in.
Conductor Count 3
Voltage Rating 600V
Ampacity Rating 70
Weight per Foot 0.548 lb

Get Product Details

Get Product Details

Specifically optimized for heavy-amperage residential branch circuits, this 4 AWG NM-B Copper Building Wire provides the heavy-duty power delivery required for modern high-performance homes. Featuring two insulated copper conductors and a dedicated bare ground wire, this assembly is engineered for interior dry-location wiring where high conductivity and long-term reliability are paramount.

Why Choose 4/3 NM-B Copper Building Wire?

This 2-conductor (with ground) cable is a staple for professional contractors handling high-load appliances. The Type NM-B construction allows for a direct pull through wooden framing members without the added labor or cost of conduit, while the solid copper core ensures minimal voltage drop over long residential runs.

  • High-Efficiency Copper Core: Annealed (soft) copper conductors offer the superior electrical performance and flexibility needed for tight residential installs.

  • Low-Friction Pulling Jacket: The slick, black PVC outer jacket is designed to slide easily through bored holes in studs and joists, reducing physical strain on the installer.

  • Integrated Safety Ground: Includes a full-sized bare copper grounding conductor to ensure immediate fault current paths and total code compliance.

  • Dual-Layer Insulation: Individual conductors are protected by heat-resistant PVC and a slick nylon topcoat (THHN/THWN-2), providing enhanced protection against abrasion.

Technical Specifications: 4/3 NM-B Copper

  • Conductor Size: 4 AWG

  • Number of Conductors: 2 (plus Ground)

  • Color Code: Black, White, Bare Ground

  • Ampacity: 70 Amps at 60°C (NEC Table 310.16)

  • Voltage: 600V

  • Insulation: Polyvinyl Chloride (PVC) with Nylon Covering (Type THHN)

  • Max Temp: 90°C (Dry locations only)

  • Conductor Material: Annealed (Soft) Copper

  • Standards: UL Standard 83, UL Standard 719, ASTM B-3, B-8, Federal Spec A-A-59544

Common Applications

  • Residential Electric Ranges: The industry standard for wiring dedicated circuits for high-wattage kitchen ranges and built-in ovens.

  • HVAC Condenser Units: Ideal for supplying power to large central air conditioning units and residential heat pump systems.

  • Home Workshop Sub-Panels: Frequently used to feed secondary 60A or 70A panels in garages or detached sheds.

  • Electric Vehicle (EV) Charging: A preferred solution for Level 2 EVSE installations that require sustained high-amperage delivery in a residential setting.


Technical Note: All values are nominal and subject to industry tolerances and manufacturer corrections. Specifications are subject to change without notice. It is the buyer’s responsibility to verify that all materials meet the specific requirements of the project and comply with local electrical codes. NM-B is for dry, indoor use only.

 

*All values are nominal and subject to correction. Ampacity is based on the National Electrical Code (NEC) 60°C column for NM-B cable, regardless of the conductor temperature rating.

See Full Specifications

See Full Specifications

Physical Specifications

Wire Size (AWG/MCM) 4 AWG
Conductor Material Copper
Conductor Type Stranded
Strand Count 7
Outer Diameter (OD) (in/mm) 0.72 in.
Jacket Type PVC
Conductor Count 3
Shield Unshielded
Insulation Type (PVC) Polyvinyl Chloride
UL Listing Numbers UL 83

Technical Specifications

Voltage Rating 600V
Ampacity Rating 70
Submersible No
Temperature Rating 90ºC
Standards US 719
UL 83
ASTM B3 and B8
Miscellaneous Information All values are nominal and subject to correction.
RoHS Compliance Yes

Usage & Installation

Primary ApplicationsWiring outlets, switches, and lighting circuits in residential buildings.

Packaging & Dimensions:

Weight per Foot 0.548 lb

Shipping and Returns

Shipping and Returns

General Shipping Information

In-stock orders placed before 3pm EST typically ship within 1-2 business days. Our business days are Monday through Friday; we do not process orders on Saturday, Sunday, or major US Holidays.

You will receive an e-mail with a tracking number within 1-2 business days from the time its shipped. You will also be able to view your order status and tracking numbers in your account order history.

Expedited Shipping

Expedited shipments are delivered Monday-Friday except on US Holidays. The order must be placed before 12pm CST to ship same day ( Mon-Fri Only).

Returns

You have 30 days from the day you receive the item to contact us for a return. Returns are subject to a 30% Restocking Fee.

Please contact us at help@wireamerica.com to request a return authorization. Have your order number or name the order was placed with ready and we will email you an RMA (return) number and instructions for return. Currently, we do not offer exchanges. A new order must be placed if you need a different item. If you provide the new order number at the time of your return request, the restocking fee may be lowered.

Orders on any items with a material value of $50 or less are non-returnable.

4/3 NM-B Copper Building Wire with Ground, 600V (Black Jacket)

Parent SKU :  NMB4-3

SKU :  NMB4-3-250

STRANDED COPPER • 600V • NON-METALLIC SHEATHED CABLE
In Stock
Ships in 1-2 days

Parent SKU :  NMB4-3

SKU :  NMB4-3-250

$3,428/ea.
$6,821/ea.
$13,572/ea.
$33,756/ea.
$13.92/ft.
Please select an option
Min: 250 ft., Max: 10,000 ft.
Spool (250 ft.)
$3,428.00
Please select an option
Maximum reached, contact us for custom orders
Contact Us
  • Fast Shipping
  • Competitive Pricing
  • Phone Support

Get Product Details

Get Product Details

Specifically optimized for heavy-amperage residential branch circuits, this 4 AWG NM-B Copper Building Wire provides the heavy-duty power delivery required for modern high-performance homes. Featuring two insulated copper conductors and a dedicated bare ground wire, this assembly is engineered for interior dry-location wiring where high conductivity and long-term reliability are paramount.

Why Choose 4/3 NM-B Copper Building Wire?

This 2-conductor (with ground) cable is a staple for professional contractors handling high-load appliances. The Type NM-B construction allows for a direct pull through wooden framing members without the added labor or cost of conduit, while the solid copper core ensures minimal voltage drop over long residential runs.

  • High-Efficiency Copper Core: Annealed (soft) copper conductors offer the superior electrical performance and flexibility needed for tight residential installs.

  • Low-Friction Pulling Jacket: The slick, black PVC outer jacket is designed to slide easily through bored holes in studs and joists, reducing physical strain on the installer.

  • Integrated Safety Ground: Includes a full-sized bare copper grounding conductor to ensure immediate fault current paths and total code compliance.

  • Dual-Layer Insulation: Individual conductors are protected by heat-resistant PVC and a slick nylon topcoat (THHN/THWN-2), providing enhanced protection against abrasion.

Technical Specifications: 4/3 NM-B Copper

  • Conductor Size: 4 AWG

  • Number of Conductors: 2 (plus Ground)

  • Color Code: Black, White, Bare Ground

  • Ampacity: 70 Amps at 60°C (NEC Table 310.16)

  • Voltage: 600V

  • Insulation: Polyvinyl Chloride (PVC) with Nylon Covering (Type THHN)

  • Max Temp: 90°C (Dry locations only)

  • Conductor Material: Annealed (Soft) Copper

  • Standards: UL Standard 83, UL Standard 719, ASTM B-3, B-8, Federal Spec A-A-59544

Common Applications

  • Residential Electric Ranges: The industry standard for wiring dedicated circuits for high-wattage kitchen ranges and built-in ovens.

  • HVAC Condenser Units: Ideal for supplying power to large central air conditioning units and residential heat pump systems.

  • Home Workshop Sub-Panels: Frequently used to feed secondary 60A or 70A panels in garages or detached sheds.

  • Electric Vehicle (EV) Charging: A preferred solution for Level 2 EVSE installations that require sustained high-amperage delivery in a residential setting.


Technical Note: All values are nominal and subject to industry tolerances and manufacturer corrections. Specifications are subject to change without notice. It is the buyer’s responsibility to verify that all materials meet the specific requirements of the project and comply with local electrical codes. NM-B is for dry, indoor use only.

 

*All values are nominal and subject to correction. Ampacity is based on the National Electrical Code (NEC) 60°C column for NM-B cable, regardless of the conductor temperature rating.

See Full Specifications

See Full Specifications

Physical Specifications

Wire Size (AWG/MCM) 4 AWG
Conductor Material Copper
Conductor Type Stranded
Strand Count 7
Outer Diameter (OD) (in/mm) 0.72 in.
Jacket Type PVC
Conductor Count 3
Shield Unshielded
Insulation Type (PVC) Polyvinyl Chloride
UL Listing Numbers UL 83

Technical Specifications

Voltage Rating 600V
Ampacity Rating 70
Submersible No
Temperature Rating 90ºC
Standards US 719
UL 83
ASTM B3 and B8
Miscellaneous Information All values are nominal and subject to correction.
RoHS Compliance Yes

Usage & Installation

Primary ApplicationsWiring outlets, switches, and lighting circuits in residential buildings.

Packaging & Dimensions:

Weight per Foot 0.548 lb

Shipping and Returns

Shipping and Returns

General Shipping Information

In-stock orders placed before 3pm EST typically ship within 1-2 business days. Our business days are Monday through Friday; we do not process orders on Saturday, Sunday, or major US Holidays.

You will receive an e-mail with a tracking number within 1-2 business days from the time its shipped. You will also be able to view your order status and tracking numbers in your account order history.

Expedited Shipping

Expedited shipments are delivered Monday-Friday except on US Holidays. The order must be placed before 12pm CST to ship same day ( Mon-Fri Only).

Returns

You have 30 days from the day you receive the item to contact us for a return. Returns are subject to a 30% Restocking Fee.

Please contact us at help@wireamerica.com to request a return authorization. Have your order number or name the order was placed with ready and we will email you an RMA (return) number and instructions for return. Currently, we do not offer exchanges. A new order must be placed if you need a different item. If you provide the new order number at the time of your return request, the restocking fee may be lowered.

Orders on any items with a material value of $50 or less are non-returnable.

Physical Specifications

Wire Size (AWG/MCM) 4 AWG
Conductor Material Copper
Conductor Type Stranded
Strand Count 7
Outer Diameter (OD) (in/mm) 0.72 in.
Jacket Type PVC
Conductor Count 3
Shield Unshielded
Insulation Type (PVC) Polyvinyl Chloride
UL Listing Numbers UL 83

Technical Specifications

Voltage Rating 600V
Ampacity Rating 70
Submersible No
Temperature Rating 90ºC
Standards US 719
UL 83
ASTM B3 and B8
Miscellaneous Information All values are nominal and subject to correction.
RoHS Compliance Yes

Usage & Installation:

Primary ApplicationsWiring outlets, switches, and lighting circuits in residential buildings.

Packaging & Dimensions:

Weight per Foot 0.548 lb

Have Questions?

Call Us. Icon

Call Us.

(833) 268-8644

Email Us

This 4 AWG, 3-conductor Non-Metallic Sheathed Cable is a heavy-gauge power cable designed for high-capacity residential branch circuits. It is the go-to choice for massive electrical loads that require a dedicated neutral and ground. Common applications include wiring for electric vehicle (EV) fast chargers, large electric ranges, commercial-grade steam showers, and 70A to 80A sub-panels. Because it is rated NM-B, it is strictly for use in dry, indoor locations.

At the 4 AWG size, copper offers excellent conductivity with a smaller diameter than aluminum, making it easier to pull through bored holes in wooden framing.

  • Integrated Ground: This cable features three insulated current-carrying conductors and one bare equipment grounding conductor, providing a complete solution for 120/240V circuits.
  • Ease of Installation: NM-B (often called Romex) eliminates the need for expensive conduit runs within interior walls. The flexible PVC jacket protects the conductors while allowing for relatively easy routing through floor joists and wall studs.
  • Reliable Performance: Copper's superior thermal properties ensure that connections at breakers and terminals remain stable under high-load cycles, such as those found in EV charging.

In accordance with NEC Article 334.80, NM-B cable must be sized based on the 60°C temperature column of the ampacity table, regardless of the higher heat rating of the internal insulation.

  • 60°C Rating: 70 Amps
  • 75°C/90°C Rating (For Derating Only): 85A / 95A

⚠️ PRO TIP: Even if your breaker is rated for 75°C, you must abide by the 60°C rule for NM-B. Consequently, a 70 Amp circuit breaker is the maximum standard protection allowed for this cable in most jurisdictions.

This cable follows standard North American color-coding for 120/240V systems:

  1. Black: Hot (Phase A)
  2. Red: Hot (Phase B)
  3. White: Neutral
  4. Bare Copper: Ground

While smaller gauges of NM-B (like 14, 12, and 10 AWG) use color-coded jackets to indicate gauge, heavy-duty sizes like 4 AWG typically utilize a Black outer jacket. The jacket is made of a tough, flame-retardant PVC that includes a nylon coating on the internal conductors for easier pulling.

While 4/3 NM-B is powerful, it has specific environmental and mechanical limitations:

  • Dry Locations Only: This cable is not rated for wet or damp locations. It cannot be used outdoors, even in conduit, as moisture can accumulate and degrade the jacket over time.
  • Physical Protection: If the cable is exposed (for example, running down a basement wall to a panel), it should be protected by a sleeve or conduit to prevent accidental impact damage.
  • Bending Radius: 4 AWG copper is quite stiff. You must maintain a bending radius of at least 5 times the cable diameter to prevent stress fractures in the copper strands or the insulation.