Physical Specifications
Technical Specifications
Packaging & Dimensions:
|
||||||||||||||||||||||||||||||||||
The overall jacket diameter for 1/0 15kV 133% URD is approximately 1.16 inches. For a single-conductor installation, a 2.5-inch conduit is standard. For a triplex configuration (three cables), a 3.5-inch to 4-inch conduit is recommended.
Note on Conduit Sizing: These recommendations are based on standard NEC 40% fill guidelines for general informational purposes. Because factors such as pull length, total degrees of bends, and pulling tension vary by project, always consult with a licensed electrical engineer or project lead to verify final conduit specifications and ensure local code compliance.
This 1/0 AWG cable features 16 x #14 AWG solid bare copper neutral wires. These wires are helically applied and uniformly spaced over the insulation shield to provide 100% (Full) conductivity relative to the 1/0 aluminum phase conductor, ensuring a safe and effective ground path.
ductor, which is a critical safety requirement for many single-phase residential primary systems.
15kV Aluminum URD (Underground Residential Distribution) cable is a medium-voltage cable used for primary underground power distribution at 15,000 volts or less. It features an aluminum conductor, solid or stranded, with Tree-Retardant Cross-Linked Polyethylene (TR-XLPE), rated for direct burial or duct installation in wet/dry locations.
RUS Accepted means this cable meets the technical and durability standards set by the Rural Utilities Service (USDA). This is a critical requirement for contractors working on federally funded rural electrification projects, as it ensures the cable is vetted for long-term reliability in utility-grade infrastructure.
The 133% insulation level provides a thicker 220-mil wall of TR-XLPE compared to the standard 175-mil wall found on standard 100% rated cables. This provides a higher safety margin and superior protection against voltage spikes, which is especially important in systems where fault-clearing times may be longer.
The minimum bending radius for 1/0 15kV URD is approximately 14 inches. Per industry standards, the radius is calculated as 12 times the overall diameter of the cable. Maintaining this radius during installation ensures that the insulation shield and concentric neutral wires are not compromised by mechanical stress.
Yes, 15kV URD Cable is rated for direct burial or installation in conduits.