2-2-2-2 Quadruplex Aluminum Direct Burial Cable, Wittenberg URD

Parent SKU :  WIT-4URD

SKU :  WIT-4URD-100

600 VOLT XLPE JACKET, SUNLIGHT RESISTANT. URD.
Wire Size 2 AWG
Conductor Material Aluminum
Conductor Type Stranded
Outer Diameter 0.97 in. / 24.638 mm
Conductor Count 4
Voltage Rating 600
Ampacity Rating 155

Get Product Details

Get Product Details

"The industry-standard for secondary three-phase residential, farm, and commercial power distribution. Engineered for reliable 600V delivery, this cable is rated for both direct burial and duct installations, featuring sunlight-resistant XLP insulation for robust, long-term underground performance."

Why Electricians Choose Wittenberg 2-2-2-2 Quadruplex Aluminum URD

The Wittenberg 2-2-2-2 URD cable is a heavy-duty solution for secondary underground three-phase power distribution. Unlike configurations with a reduced neutral, the Wittenberg features four full-sized #2 AWG conductors. This makes it the ideal choice for applications with significant single-phase loads on a three-phase system, ensuring the neutral can safely handle the return current. By utilizing high-conductivity 1350-H19 aluminum and a heavy-duty, sunlight-resistant XLP insulation, it offers superior resistance to environmental degradation and moisture.

  • Full-Neutral Performance: Featuring a full-sized #2 AWG neutral conductor for better handling of unbalanced loads.

  • 600V Reliability: Rated for continuous operation in wet or dry locations at temperatures up to 90°C.

  • Sunlight-Resistant XLP: Advanced cross-linked polyethylene insulation prevents premature aging from UV exposure at service heads.

  • Direct Burial Ready: Engineered for underground utility distribution; can be installed directly in the earth or within conduit systems.

Technical Specifications: 2-2-2-2 Aluminum URD

ENGINEERING OVERVIEW: 2-2-2-2 Quadruplex URD

  • Application: Three-phase secondary underground distribution; 100A services with unbalanced loads.

  • Voltage Rating: 600 Volts.

  • UL Listing: UL 854 (Service-Entrance Cable).

  • Conductor Material: Concentric stranded 1350-H19 series aluminum.

  • Phase Insulation: Black sunlight-resistant XLP (Cross-Linked Polyethylene).

  • Neutral Insulation: Black XLP with 3 extruded yellow stripes.

  • Temperature Rating: 90°C (Wet or Dry).

  • Cable Outer Diameter: 0.97 inches (24.64 mm).

  • Ampacity (Direct Burial): 155 Amps.

  • Ampacity (In Duct): 115 Amps.

  • Compliance Standards: UL 854; Type USE-2; RUS Accepted; ASTM B-230, B-231, B-609, B-901.

Common 2-2-2-2 Aluminum URD Applications

  • Commercial 3-Phase Service: Perfect for small retail or office spaces where a 100-Amp 3-phase service is required.

  • Unbalanced Load Scenarios: The go-to cable for 3-phase systems that also feed many 120V single-phase circuits (like lighting and office equipment), requiring a full-sized neutral.

  • Agricultural Equipment: Ideal for powering farm machinery and processing units that require a stable, high-capacity neutral.

  • Site Infrastructure: Used for community centers or shared residential amenities where power demands vary significantly across the three phases.

 


Technical Note: All values are nominal and subject to industry tolerances and manufacturer corrections. Specifications are subject to change without notice. It is the buyer’s responsibility to verify that all materials meet the specific requirements of the project and comply with local electrical codes.

Ampacity: 90°C conductor temperature, 20°C ambient temperature, RHO 90, 100% load factor. Single and Quadruplex based on 3/C. Neutral wire carries unbalanced load only. Reference NEC article 310.15 for NEC installations.

 

See Full Specifications

See Full Specifications

Physical Specifications

Wire Size (AWG/MCM) 2 AWG
Conductor Material Aluminum
Conductor Type Stranded
Strand Count 7
Outer Diameter (OD) (in/mm) 0.97 in. / 24.638 mm
Jacket Type XLPE
Conductor Count 4
Shield Unshielded
Insulation Type (XLPE) Cross-Linked Polyethylene

Technical Specifications

Voltage Rating 600
Ampacity Rating 155
Direct Burial Rating Yes
Submersible No
Flexibility Rating Medium
Sunlight Resistance Rating Yes
Temperature Rating 90ºC
Standards ASTM B-230 Aluminum 1350-H19 Wire for Electrical Purposes
ASTM B-231 Concentric-Lay-Stranded Aluminum 1350 Conductors
ASTM B-609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
ASTM B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction
ICEA S-105-692 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables
Federal Specification A-A-59544A
UL 854 Service-Entrance Cables
Sunlight Resistant
RUS Accepted
Miscellaneous Information All values are nominal and subject to correction. *Not RUS accepted size **Ampacity: 90°C conductor temperature, 20°C ambient temperature, RHO 90, 100% load factor. Single and Quadruplex based on 3/C. Neutral wire carries unbalanced load only. Reference NEC article 310.15 for NEC installations.

Usage & Installation

Primary ApplicationsUnderground Secondary Power Distribution
Common Uses
  • Single-family homes
  • Apartment complexes
  • Farms
  • Smaller commercial buildings.

Packaging & Dimensions:

Weight per Foot 0.389 lb

Shipping and Returns

Shipping and Returns

General Shipping Information

In-stock orders placed before 3pm EST typically ship within 1-2 business days. Our business days are Monday through Friday; we do not process orders on Saturday, Sunday, or major US Holidays.

You will receive an e-mail with a tracking number within 1-2 business days from the time its shipped. You will also be able to view your order status and tracking numbers in your account order history.

Expedited Shipping

Expedited shipments are delivered Monday-Friday except on US Holidays. The order must be placed before 12pm CST to ship same day ( Mon-Fri Only).

Returns

You have 30 days from the day you receive the item to contact us for a return. Returns are subject to a 30% Restocking Fee.

Please contact us at help@wireamerica.com to request a return authorization. Have your order number or name the order was placed with ready and we will email you an RMA (return) number and instructions for return. Currently, we do not offer exchanges. A new order must be placed if you need a different item. If you provide the new order number at the time of your return request, the restocking fee may be lowered.

Orders on any items with a material value of $50 or less are non-returnable.

Aluminum Quadruplex Direct Burial URD

Wire America | Wire Flexibility Series

This video shows the flexibility, size, jacket detail, conductor material and stranding of the Dyke 2 Gauge, 4 Conductor Quadruplex URD, Aluminum Direct Burial Cable.

2-2-2-2 Quadruplex Aluminum Direct Burial Cable, Wittenberg URD

Parent SKU :  WIT-4URD

SKU :  WIT-4URD-100

600 VOLT XLPE JACKET, SUNLIGHT RESISTANT. URD.
In Stock
Ships in 1-2 days

Parent SKU :  WIT-4URD

SKU :  WIT-4URD-100

$233/ea.
$574/ea.
$1,142/ea.
$2,272/ea.
$2.33/ft.
Please select an option
Min: 100 ft., Max: 20,000 ft.
Spool (100 ft.)
$233.00
Please select an option
Maximum reached, contact us for custom orders
Contact Us
  • Fast Shipping
  • Competitive Pricing
  • Phone Support

Get Product Details

Get Product Details

"The industry-standard for secondary three-phase residential, farm, and commercial power distribution. Engineered for reliable 600V delivery, this cable is rated for both direct burial and duct installations, featuring sunlight-resistant XLP insulation for robust, long-term underground performance."

Why Electricians Choose Wittenberg 2-2-2-2 Quadruplex Aluminum URD

The Wittenberg 2-2-2-2 URD cable is a heavy-duty solution for secondary underground three-phase power distribution. Unlike configurations with a reduced neutral, the Wittenberg features four full-sized #2 AWG conductors. This makes it the ideal choice for applications with significant single-phase loads on a three-phase system, ensuring the neutral can safely handle the return current. By utilizing high-conductivity 1350-H19 aluminum and a heavy-duty, sunlight-resistant XLP insulation, it offers superior resistance to environmental degradation and moisture.

  • Full-Neutral Performance: Featuring a full-sized #2 AWG neutral conductor for better handling of unbalanced loads.

  • 600V Reliability: Rated for continuous operation in wet or dry locations at temperatures up to 90°C.

  • Sunlight-Resistant XLP: Advanced cross-linked polyethylene insulation prevents premature aging from UV exposure at service heads.

  • Direct Burial Ready: Engineered for underground utility distribution; can be installed directly in the earth or within conduit systems.

Technical Specifications: 2-2-2-2 Aluminum URD

ENGINEERING OVERVIEW: 2-2-2-2 Quadruplex URD

  • Application: Three-phase secondary underground distribution; 100A services with unbalanced loads.

  • Voltage Rating: 600 Volts.

  • UL Listing: UL 854 (Service-Entrance Cable).

  • Conductor Material: Concentric stranded 1350-H19 series aluminum.

  • Phase Insulation: Black sunlight-resistant XLP (Cross-Linked Polyethylene).

  • Neutral Insulation: Black XLP with 3 extruded yellow stripes.

  • Temperature Rating: 90°C (Wet or Dry).

  • Cable Outer Diameter: 0.97 inches (24.64 mm).

  • Ampacity (Direct Burial): 155 Amps.

  • Ampacity (In Duct): 115 Amps.

  • Compliance Standards: UL 854; Type USE-2; RUS Accepted; ASTM B-230, B-231, B-609, B-901.

Common 2-2-2-2 Aluminum URD Applications

  • Commercial 3-Phase Service: Perfect for small retail or office spaces where a 100-Amp 3-phase service is required.

  • Unbalanced Load Scenarios: The go-to cable for 3-phase systems that also feed many 120V single-phase circuits (like lighting and office equipment), requiring a full-sized neutral.

  • Agricultural Equipment: Ideal for powering farm machinery and processing units that require a stable, high-capacity neutral.

  • Site Infrastructure: Used for community centers or shared residential amenities where power demands vary significantly across the three phases.

 


Technical Note: All values are nominal and subject to industry tolerances and manufacturer corrections. Specifications are subject to change without notice. It is the buyer’s responsibility to verify that all materials meet the specific requirements of the project and comply with local electrical codes.

Ampacity: 90°C conductor temperature, 20°C ambient temperature, RHO 90, 100% load factor. Single and Quadruplex based on 3/C. Neutral wire carries unbalanced load only. Reference NEC article 310.15 for NEC installations.

 

See Full Specifications

See Full Specifications

Physical Specifications

Wire Size (AWG/MCM) 2 AWG
Conductor Material Aluminum
Conductor Type Stranded
Strand Count 7
Outer Diameter (OD) (in/mm) 0.97 in. / 24.638 mm
Jacket Type XLPE
Conductor Count 4
Shield Unshielded
Insulation Type (XLPE) Cross-Linked Polyethylene

Technical Specifications

Voltage Rating 600
Ampacity Rating 155
Direct Burial Rating Yes
Submersible No
Flexibility Rating Medium
Sunlight Resistance Rating Yes
Temperature Rating 90ºC
Standards ASTM B-230 Aluminum 1350-H19 Wire for Electrical Purposes
ASTM B-231 Concentric-Lay-Stranded Aluminum 1350 Conductors
ASTM B-609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
ASTM B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction
ICEA S-105-692 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables
Federal Specification A-A-59544A
UL 854 Service-Entrance Cables
Sunlight Resistant
RUS Accepted
Miscellaneous Information All values are nominal and subject to correction. *Not RUS accepted size **Ampacity: 90°C conductor temperature, 20°C ambient temperature, RHO 90, 100% load factor. Single and Quadruplex based on 3/C. Neutral wire carries unbalanced load only. Reference NEC article 310.15 for NEC installations.

Usage & Installation

Primary ApplicationsUnderground Secondary Power Distribution
Common Uses
  • Single-family homes
  • Apartment complexes
  • Farms
  • Smaller commercial buildings.

Packaging & Dimensions:

Weight per Foot 0.389 lb

Shipping and Returns

Shipping and Returns

General Shipping Information

In-stock orders placed before 3pm EST typically ship within 1-2 business days. Our business days are Monday through Friday; we do not process orders on Saturday, Sunday, or major US Holidays.

You will receive an e-mail with a tracking number within 1-2 business days from the time its shipped. You will also be able to view your order status and tracking numbers in your account order history.

Expedited Shipping

Expedited shipments are delivered Monday-Friday except on US Holidays. The order must be placed before 12pm CST to ship same day ( Mon-Fri Only).

Returns

You have 30 days from the day you receive the item to contact us for a return. Returns are subject to a 30% Restocking Fee.

Please contact us at help@wireamerica.com to request a return authorization. Have your order number or name the order was placed with ready and we will email you an RMA (return) number and instructions for return. Currently, we do not offer exchanges. A new order must be placed if you need a different item. If you provide the new order number at the time of your return request, the restocking fee may be lowered.

Orders on any items with a material value of $50 or less are non-returnable.

Video thumbnail
Aluminum Quadruplex Direct Burial URD

Wire America | Wire Flexibility Series

This video shows the flexibility, size, jacket detail, conductor material and stranding of the Dyke 2 Gauge, 4 Conductor Quadruplex URD, Aluminum Direct Burial Cable.

Physical Specifications

Wire Size (AWG/MCM) 2 AWG
Conductor Material Aluminum
Conductor Type Stranded
Strand Count 7
Outer Diameter (OD) (in/mm) 0.97 in. / 24.638 mm
Jacket Type XLPE
Conductor Count 4
Shield Unshielded
Insulation Type (XLPE) Cross-Linked Polyethylene

Technical Specifications

Voltage Rating 600
Ampacity Rating 155
Direct Burial Rating Yes
Submersible No
Flexibility Rating Medium
Sunlight Resistance Rating Yes
Temperature Rating 90ºC
Standards ASTM B-230 Aluminum 1350-H19 Wire for Electrical Purposes
ASTM B-231 Concentric-Lay-Stranded Aluminum 1350 Conductors
ASTM B-609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
ASTM B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction
ICEA S-105-692 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables
Federal Specification A-A-59544A
UL 854 Service-Entrance Cables
Sunlight Resistant
RUS Accepted
Miscellaneous Information All values are nominal and subject to correction. *Not RUS accepted size **Ampacity: 90°C conductor temperature, 20°C ambient temperature, RHO 90, 100% load factor. Single and Quadruplex based on 3/C. Neutral wire carries unbalanced load only. Reference NEC article 310.15 for NEC installations.

Usage & Installation:

Primary ApplicationsUnderground Secondary Power Distribution
Common Uses
  • Single-family homes
  • Apartment complexes
  • Farms
  • Smaller commercial buildings.

Packaging & Dimensions:

Weight per Foot 0.389 lb

Have Questions?

Call Us. Icon

Call Us.

(833) 268-8644

Email Us

The key difference is the neutral wire size. Both cables have three #2 AWG phase conductors, but while the 2-2-2-4 has a reduced #4 AWG neutral, the 2-2-2-2 Wittenberg features a full #2 AWG neutral. Wittenberg is preferred when the electrical system anticipates more "unbalanced" current returning through the neutral wire.

  • Direct Burial: Approximately 155 Amps
  • In Duct/Conduit: Approximately 115 Amps

Note: These ratings are based on 90°C conductor temperature. Always consult NEC Table 310.15 for specific installation derating.

URD stands for Underground Residential Distribution. This is a specific classification of electrical cable designed to carry power from utility transformers to secondary service entrances (like your home or a commercial sub-panel). Because this is a URD cable, it is engineered with rugged XLP insulation that allows it to be buried directly in the earth without the need for a protective conduit. While it has "Residential" in the name, it is the industry standard for underground power in commercial, agricultural, and industrial applications as well.

In the electrical industry, URD cables are named after birds or colleges to simplify ordering. "Wittenberg" specifically identifies the 2-2-2-2 construction. Using the code name ensures you receive the version with the full-sized #2 neutral, whereas the code name "Dyke" would get you the version with a smaller #4 neutral.

Yes, specifically for future-proofing. While some smaller chargers only require a reduced neutral, many commercial Level 2 charging pedestals and rapid-charging systems benefit from a full-sized neutral to handle potential harmonic distortion and unbalanced loads. By installing Wittenberg #2 now, you ensure the underground infrastructure is robust enough to handle high-demand, continuous charging cycles without the neutral conductor becoming a bottleneck as the site’s power needs grow.

Important: Always consult a licensed electrical installer who is up to date on all local codes before selecting a size.

Yes. Wittenberg 2-2-2-2 is a URD Type USE-2 cable designed for direct burial. Its XLP insulation is built to handle the mechanical stress and moisture found in underground trenches without the need for conduit.

Aluminum URD is the industry standard for underground utility feeds because it is significantly more cost-effective and lighter than copper.